Insulation Resistance Test Readings Explained: What the Numbers Mean
Insulation resistance testing measures how well the insulation around cables stops current leaking between conductors or to earth. Readings are given in megohms. High readings are good; low readings point to damp, damage or ageing insulation. This guide explains how the test works, what the readings mean and what happens when a circuit fails.
What the Test Does
The electrician isolates the circuit, disconnects sensitive equipment and applies a test voltage, usually 500 V DC for domestic circuits, between conductors. The tester measures the resistance of the insulation between them.
The test is done between:
- Live and neutral.
- Live and earth.
- Neutral and earth.
Often, live and neutral are linked and tested together to earth.
What the Readings Mean
| Reading | What it usually means |
|---|---|
| Over 200 MΩ (shown as ">") | Excellent, typical of good modern cable |
| 20 to 200 MΩ | Generally good |
| 2 to 20 MΩ | Acceptable but worth noting, especially on newer cable |
| 1 to 2 MΩ | Minimum acceptable for most circuits; investigate trend |
| Below 1 MΩ | Fails the minimum standard; find the cause |
| Near zero | Short circuit or severe fault |
BS 7671 sets 1 MΩ as the minimum for circuits tested at 500 V. A good installation will be far higher.
Common Causes of Low Readings
- Damp: water in back boxes, junction boxes or outdoor fittings.
- Ageing: rubber or old PVC insulation breaking down.
- Damage: nails, screws or rodents.
- Connected equipment: appliances or surge protectors left connected can lower readings.
- Heat: cables run near heat sources or in insulation without derating.
Finding the Cause
- Disconnect all equipment and repeat.
- Split the circuit at junctions or accessories to see which section is low.
- Inspect accessories in the low section.
- Check outdoor fittings and those in bathrooms or cellars.
- Repeat after drying if damp is suspected.
Why the Test Matters
Low insulation resistance can lead to:
- RCD trips, sometimes intermittent.
- Earth leakage that makes metalwork live.
- Overheating and fire risk at damaged points.
Readings in Older Bath Homes
Cables in Georgian and Victorian homes are often in walls that hold moisture, cellars with damp and lofts with leaks. Readings may be lower than in modern homes and vary with the weather. A falling trend between inspections is a sign that the wiring needs attention.
After Water Damage
Insulation resistance testing is the main test after leaks and floods. Circuits are tested before reconnection and retested after drying. See electrics after water damage.
Frequently Asked Questions
Can I do an insulation resistance test myself?
No. It uses high voltage and needs isolation and specialist equipment.
Will the test damage my appliances?
Sensitive equipment is disconnected first to avoid this.
Does a low reading mean I need a rewire?
Not always. Often one fitting or section is the cause.
Is the reading on my EICR?
Yes, in the schedule of test results.
Concerned About Test Results?
Call us to explain your readings or find the fault. See EICR codes explained.